Recommended Rack Configuration
Learn about the locations of major rack components in a recommended ORv3 rack system configuration.
The third-party integrated ORv3 rack is a 44 OU rack assembly, with OU 1 representing the bottom-most rack-unit position and OU 44 representing the top-most rack-unit position. The recommended rack configuration for a fully populated integrated ORv3 rack system can contain the following components:
- Up to 16 QFX5250-64OE-L liquid-cooled switches (2 OU each)
- One EX4400-48T-DC-T1 management switch (1 OU)
- Up to three power shelves (1 OU each)
- Up to eighteen PSUs (six per power shelf)
- Up to three power controllers (one per power shelf)
- One rack stiffener
- Seven reserved rack units (OU 1, OU 4, OU 21, OU 24, OU 25, OU 42, and OU 44)
The locations of all switches, power shelves, adapter kits, structural components, and reserved rack units are shown in Table 1.
| Rack Unit(s) | Installed Component |
|---|---|
| OU 44 | Reserved |
| OU 43 | Power shelf 03 with 19-to-21-in. adapter kit |
| OU 42 | Reserved |
| OU 41-40 | QFX5250-64OE-L switch |
| OU 39-38 | QFX5250-64OE-L switch |
| OU 37-36 | QFX5250-64OE-L switch |
| OU 35-34 | QFX5250-64OE-L switch |
| OU 33-32 | QFX5250-64OE-L switch |
| OU 31-30 | QFX5250-64OE-L switch |
| OU 29-28 | QFX5250-64OE-L switch |
| OU 27-26 | QFX5250-64OE-L switch |
| OU 25 | Reserved |
| OU 24 | Reserved |
| OU 23 | Rack stiffener |
| OU 22 | EX4400-48T-DC-T1 ORv3 switch with ORv3 tray |
| OU 21 | Reserved |
| OU 20-19 | QFX5250-64OE-L switch |
| OU 18-17 | QFX5250-64OE-L switch |
| OU 16-15 | QFX5250-64OE-L switch |
| OU 14-13 | QFX5250-64OE-L switch |
| OU 12-11 | QFX5250-64OE-L switch |
| OU 10-9 | QFX5250-64OE-L switch |
| OU 8-7 | QFX5250-64OE-L switch |
| OU 6-5 | QFX5250-64OE-L switch |
| OU 4 | Reserved |
| OU 3 | Power shelf 02 with 19-to-21-in. adapter kit |
| OU 2 | Power shelf 01 with 19-to-21-in. adapter kit |
| OU 1 | Reserved |
QFX5250 Switches
The QFX5250 switches are the primary networking devices installed in the third-party integrated ORv3 rack and provide the switching functionality required for the deployment. Each QFX5250 switch occupies 2 OU of rack space. In the recommended rack configuration, QFX5250 switches are installed in the following rack-unit ranges:
- OU 5 through OU 20 in the bottom half of the rack
- OU 26 through OU 41 in the top half of the rack
Each QFX5250 switch is installed using a 1 OU mounting rail. The mounting rail is installed in the lower rack unit of the assigned OU pair and does not require additional rack space. For example, switches installed in OU 5–6, OU 7–8, and OU 40–41 use mounting rails installed in OU 5, OU 7, and OU 40, respectively.
To install the QFX5250 switch on the third-party integrated ORv3 rack, see How to Install QFX5250-64OE-L Switch in Third-Party Integrated ORv3 Rack.
EX4400 Switch
The EX4400 switch provides rack-level management services for the deployed QFX5250 switch infrastructure. The EX4400 serves as the out-of-band (OOB) management switch for the rack. The dedicated management ports of the QFX5250 switches installed in the rack connect to the EX4400, providing access to the management network. The recommended configuration includes an EX4400 switch installed at OU 22. This location provides convenient access for rack management and service operations.
The recommended configuration includes 1 OU rack mounting rails to support installation of both the QFX5250 switches and the EX4400 switch.
To install the EX4400 management switch on the third-party integrated ORv3 rack, see How to Install EX4400 Management Switch with Tray Assembly (1OU) in HPE Third-Party Integrated ORv3 Rack.
Power Shelves
The rack configuration includes three 1 OU, 33 kW power shelves mounted using 19-in.-to-21-in. adapter rail kits. The adapter rail kits are provided at each power-shelf location, enabling installation of ORv3 power shelves within the rack structure.
The power shelves are placed in the bottom and top sections of the rack:
- Power Shelf 01—OU 2 (bottom-of-rack)
- Power Shelf 02—OU 3 (bottom-of-rack)
- Power Shelf 03—OU 43 (top-of-rack)
This arrangement distributes the power infrastructure between the top and bottom of the rack while maximizing the available space for QFX5250 switch installations.
Depending on deployment requirements, a power shelf may alternatively be installed in position OU 24 in the middle section of the rack.
Reserved Rack Units
Reserved rack units provide clearance for installation, maintenance access, cable routing, airflow management, future expansion, and serviceability. Several rack-unit positions are intentionally reserved in the sample configuration:
- OU 1
- OU 4
- OU 21
- OU 24
- OU 25
- OU 42
- OU 44
Rack unit OU 24 includes a preinstalled 1 U mounting rail and is reserved for optional power-shelf installation in the middle of the rack.
The specific use of reserved rack units may vary depending on the final deployment configuration and future rack expansion plans.
DC Busbar
The DC busbar is mounted along the center rear of the rack. This location provides a centralized power-distribution path for the power shelves and installed rack equipment.
Liquid-Cooling Manifolds
The liquid-cooling manifolds are mounted along the rear of the rack on either side of the DC busbar in the recommended rack configuration. The supply and return manifold assemblies span the height of the rack to support coolant routing for the installed liquid-cooled switches.