Third-Party Integrated ORv3 Rack Components and Specifications

Learn about the major rack, power, cooling, and accessory components that make up the HPE third-party integrated ORv3 rack system, along with their key specifications and functions.

The HPE third-party integrated ORv3 rack system consists of several mechanical, power, cooling, and installation-related components.

The ORv3 rack is the primary structural component of the HPE third-party integrated ORv3 rack system. It consists of the OCP-compliant, ORv3 rack frame, rack assembly of 44 OU rack units, and side panels (left and right). The integrated third-party ORv3 rack provides the mechanical enclosure required to support the installed networking, power, and cooling components. The rack is designed to handle a static load of 3527.39 lb (1600 kg) and a dynamic load of 3086.47 lb (1400 kg). The side panels are a part of the HPE third-party integrated ORv3 rack.

Table 1: Third-Party ORv3 Rack Components
Component Category Key Specifications Optional Accessory
ORv3 rack (frame, left panel, right panel) Rack OCP-compliant ORv3 rack assembly, 44 OU, 750-mm width, 48-inch depth, black finish No
Levelers Rack accessory Set of four leveling feet, preinstalled No
Casters Rack accessory Set of four casters rated at 1500 lb (680.38 kg) each for rack transportation and positioning No
1400-A busbar mounting kit Power and rack accessory Supports installation of 1400-A DC busbars No
Manifold and stiffener kit Cooling and rack accessory Includes liquid-cooling distribution manifolds with 16 UQDB06 quick-disconnect ports and rack stiffener hardware No
OU labels Rack accessory Set of four rack-unit labels No
Rack and stack packaging Packaging Rack packaging for stacking and transportation Yes
Ramp for 750-mm pallet Packaging Ramp for moving the rack from a 750-mm-wide pallet Yes
Rack and stack (RNS) crate Packaging One international heat-treated RNS crate with ramp Yes
ORv3 rack mount kit (RMK) Rack accessory Eighteen 1 OU, mounting rail-pair kits containing matched left and right rails No
Power shelf adapter kit Rack accessory Three 1 OU adapter rail kits for mounting the 19-in. power shelves in the 21-in. ORv3 racks. Each kit contains one left rail and one right rail and supports a single power shelf. No
DC busbar Power One 1400-A DC busbar rated for up to 72 kW power-distribution capacity No
Power shelf kit Power Three 1 OU, 33kW, 50-V DC, air-cooled power shelves in a 19-in. form factor. No
Power supply unit (PSU) Power PSU is installed in the power shelf. Six PSUs are required per shelf, each supplying 5.5 kW power. No (part of power shelf kit)
Power management controller (PMC) Power Power management controller is installed in the power shelf. One PMC is required per shelf. No (part of power shelf kit)
Table 2: Physical Specifications of Third-Party Integrated ORv3 Rack Components
Component Gross Weight (lb) Net Weight (lb) Length (cm) Width (cm) Height (cm)

ORv3 rack (includes left and right side panels)

920 lb (417.30 kg) 900 lb (408.23 kg) 67 46 102

International heat-treated crate

300 lb (136.97 kg) 300 lb (136.07 kg) 67 46 102

Liquid-cooled manifold

254 lb (115.21 kg) 176 lb (79.83 kg) 223 41 18

ORv3 rack mounting rail kit (1 OU)

1.45 lb (0.65 kg) 1.45 lb (0.65 kg) 78.1 2.5 4.7

DC busbar (72 kW)

3.2 lb (1.45 kg) 3.2 lb (1.45 kg) 74.8 4.6 4.5

19-in. to 21-in. power shelf adapter kit (1 OU)

1.45 lb (0.65 kg) 1.45 lb (0.65 kg) 74.8 4.6 4.5

Power shelf (19-inch)

22.05 lb (10.00 kg) 22.05 lb (10.00 kg) 10.2 12.7 25.4
Note:

The adapter kit converts a 19-in. chassis width to standard 21-in. EIA mounting-hole spacing while providing support for the wider shelf.

For information about the part numbers and ordering information, see the Next Generation Quoter tool.

Figure 1: HPE Third-Party Integrated ORv3 Rack with Components HPE Third-Party Integrated ORv3 Rack with Components

International Heat-Treated Rack and Stack Crate

The international heat-treated rack and stack (RNS) crate is the ISPM 15-compliant shipping container used to transport the fully-assembled ORv3 rack and associated rack components. The RNS crate protects the fully assembled rack and associated subassemblies during shipment, handling, and storage before installation.

The crate includes a built-in deployment ramp to facilitate movement of the rack from the shipping pallet to the installation location. The rack is shipped fully assembled within the crate. The crate also includes anchor-hole hardware for rack securing and, for international shipments, desiccant bags to protect the rack from mold, rust, and damage during transport and storage.

Note:

Retain the crate, ramp, and packaging materials for future transportation or storage requirements.

Table 3: Packaging Dimensions
Height Width Depth
106.8 in. (271.3 cm) 45 in. (114.3 cm) 65 in. (165.1 cm)
Figure 2: International Heat-Treated RNS Crate International Heat-Treated RNS Crate

ORv3 Rack Mount Kit

The ORv3 rack mount kit (RMK) includes the rails, brackets, and associated hardware required to securely install and support equipment within the rack. These components provide the mechanical interface between the rack and the installed networking equipment and help ensure proper alignment, support, and serviceability.

Figure 3: ORv3 Rack Mount Kit ORv3 Rack Mount Kit

Rack Stiffener

The rack stiffener is a structural component that increases rack rigidity and helps maintain mechanical stability under installed equipment loads. For rack configurations containing multiple QFX5250 switches, power components, and liquid-cooling infrastructure, the stiffener provides the required stability.

Levelers

Levelers are adjustable support feet installed at the base of the rack. After positioning the rack at its installation location, you use levelers to level and stabilize the rack. Levelers ensure proper weight distribution and mechanical stability.

Casters

Casters are installed at the base of the rack and enable controlled movement of the rack during transportation and positioning. After you have moved the rack to its final location, use levelers to support and stabilize the rack.

Power Shelf Adapter Kit

Use the power shelf adapter kit to install a 19-in. ORv3 power shelf within a 21-in. ORv3 mounting environment. Each kit includes a left and right adapter rail and supports a single power shelf installation. The adapter kit provides the mechanical interface required to securely mount the power shelf within the rack.

Figure 4: Power Shelf Adapter Kit Power Shelf Adapter Kit

Liquid-Cooling Manifolds

The liquid-cooling manifolds distribute facility coolant within the rack. Located along the rear of the rack on either side of the DC busbar, the manifold assembly includes dedicated supply and return manifolds with quick-disconnect inlet and outlet ports. The supply manifold delivers coolant to the liquid-cooled QFX5250 switches installed in the integrated ORv3 rack, while the return manifold returns coolant from the switches to the facility cooling system. The manifold system forms the primary cooling-distribution infrastructure for the liquid-cooled switches in the ORv3 rack.

Key specifications include:

  • Separate supply and return manifold assemblies
  • ORv3 blind-mate manifold interface
  • Sixteen UQDB06 quick-disconnect ports per manifold
  • Sixteen branches per supply manifold
  • Sixteen branches per return manifold
  • SUS316L stainless-steel manifold bodies
  • Integrated air-vent valves
  • Integrated end plugs and sealing components
  • RoHS compliance

Note: The liquid-cooling manifold assembly is shipped with:
  • Protective port covers installed to prevent dust and debris contamination during handling, transportation, and storage.

  • Nitrogen gas (25–26 psi) to maintain internal cleanliness during transportation and storage.

CAUTION:

Keep all manifold ports and fittings free of dirt, oil, grease, and other contaminants during installation. Contamination can affect cooling-system performance and reliability.

Figure 5: Liquid-Cooling Manifolds Liquid-Cooling Manifolds

DC Busbar

The DC busbar serves as the primary power distribution device for the devices installed in the ORv3 rack. The busbar distributes 48-V DC power from the power shelves to the networking devices and other rack components. Located along the center rear of the rack, the busbar has a current rating of 1400 A and provides up to 72 kW of rack-level power distribution capacity. The busbar enables centralized power delivery and simplifies power distribution throughout the rack.

Figure 6: DC Busbar DC Busbar

Power Shelf

The power shelf is the central power delivery subsystem of the rack. It houses the power supply units (PSUs) and power management controller (PMC) within a 1 OU rack-unit form factor and interfaces directly with the DC busbar. The power shelf receives facility power and provides regulated 50-V DC power for distribution throughout the rack. Each power shelf provides up to 33 kW of output power and supports installation of up to six PSUs and one power controller.

The air-cooled power shelf includes the following components:

  • PSUs—The PSUs convert facility input power into 48-V DC output power for use by the rack equipment. The PSUs are installed within the power shelf and are field-replaceable to simplify maintenance and service operations. Each power shelf supports six PSUs. Together, these PSUs provide a maximum shelf output capacity of 33 kW, with each PSU producing 5.5 kW.

  • Power controller—The controller monitors and manages operation of the power shelf, installed PSUs, and DC busbar. It provides monitoring, control, health-reporting, and alarm-management functions that help ensure reliable rack power delivery and facilitate troubleshooting. Each power shelf contains one power controller, which provides visibility into shelf status, PSU health, power distribution status, alarms, and operational telemetry.

Figure 7: Power Shelf, PSUs, and Power Shelf Controller Power Shelf, PSUs, and Power Shelf Controller